We use cookies to improve your experience on our website, to personalise content and ads, to provide social media features and to analyse our traffic. We also share information about your use of our website with our social media, advertising and analytics partners, who may combine it with other information that you have provided to them or that they have collected from your use of their services. Please click [Accept All Cookies] if you agree with the use of all of our cookies. Please click [Cookies Settings] to customise your cookies settings on our website.Cookies Policy

MMP-T32 25A

Material number 600201
Motor circuit breaker;200-690V; 11kW(at 400V);50/60Hz; 18-25A; without UL

FA-MMS: Manual Motor Starter

SeriesMMP-T SERIES
TypeMOTOR CIRCUIT BREAKERS
Compliant with Standard(s)IEC 60947-2, GB14048.2, EN 60947-4-1, EN 60947-2, JIS C8201-2-1 ANN.1, JIS 8201-4-1, IEC 60947-4-1
Frame Size32
Number of Poles3
Rated Current (A)25
Rated Voltage (V)690
Frequency Range (Hz)50/60
Rated Capacity (kW)10.6
Heater Designation (A)25
Range of Setting Current (A)18-25
Breaking Capacity at 415V (kA)ICU: 50; ICS: 38
Electrical Durability (Load)100000 OPERATIONS
Mech. Durability (at no Load)100000 OPERATIONS
WiringSCREW-CLAMP
Automatic Tripping DeviceTHERMAL-MAGNETIC (ADJUSTABLE)

Product Dimensions & Weight

Depth (mm)82
Weight (kg)0.33
Width (mm)45
Height (mm)90

Conformity

CECOMPLIANT
EACNON-COMPLIANT
UKCACOMPLIANT

Product Packaging

Aluminum (g)0
Others (g)0
Styrofoam (g)0
Cardboard (g)0
Steel (g)0
Glass (g)0
Other plastic (g)0
Wood (g)0
Other paper (g)54

Environmental

REACH Limit ExceededNO
RoHS ComplianceCOMPLIANT
Dangerous Goods ClassNO
WEEEB2B
Dangerous Goods IdentifierNO