Circuit-breaker; In max=1600A; Icu=Ics=65kA at AC 500V; with relay base; 5a5b

FA-ACB: Air Circuit Breaker

SeriesWS-V SERIES - ACB
TypeAE-SW - LV AIR CIRCUIT BREAKER
Current Range Ir (A)800-1600
Current TypeAC
Rated Voltage (V)690
Number of Poles3
Cycles with Rated Current5000
Cycles without Rated Current25000
Frame Size1600
Breaking Capacity at 500V (kA)65
No of Auxiliary Contacts NO5
No of Auxiliary Contacts NC5
Internal Power Supply (V)100-240 AC 100-125 DC

Product Dimensions & Weight

Width (mm)340
Height (mm)410
Depth (mm)290
Weight (kg)42

Conformity

CECOMPLIANT
EACCOMPLIANT
Shipping ApprovalsABS,BV,CCS,DNV,GL,LR,NK

Product Packaging

Cardboard (g)2500
Other paper (g)0
Aluminum (g)0
Steel (g)0
Styrofoam (g)0
Other plastic (g)0
Wood (g)7000
Glass (g)0
Others (g)0

Environmental

REACH Limit ExceededNO
RoHS ComplianceCOMPLIANT